7–2

Troubleshooting

Publication 1771Ć6.5.130 Ć May 1999

Table 7.A shows LED indications and probable causes and
recommended actions to correct common faults.

Table 7.A

Troubleshooting Chart for Thermocouple/Millivolt Input

Module (1771-IXE/D)

Indication

Probable Cause

Recommended Action

Both LEDs are OFF

No power to module

Possible short on the module

LED driver failure

Check power to I/O chassis. Recycle as

necessary.

Replace module.

Red FLT LED ON and

Green RUN LED is ON

Microprocessor, oscillator or EPROM failure

Replace module.

Red FLT LED ON

If immediately after power-up, indicates RAM or

EPROM failure.

1

Replace module.

If during operation, indicates possible

microprocessor or backplane interface failure.

1

Replace module.

Green RUN LED is flashing

Power-up diagnostics successfully completed.

Normal operation.

If LED continues to flash, and write block transfers

(BTW) cannot be accomplished, you have a

possible interface failure.

Replace module.

1

When red LED is on, the watchdog timer has timed out and backplane communications are terminated. Your user program should

monitor

communication.

Status Reported in Word 1

Design your program to monitor status bits in the lower byte of word
1, and to take appropriate action depending on your application
requirements. You may also want to monitor these bits while
troubleshooting with your industrial terminal. The module sets a bit
(1) to indicate it has detected one or more of the following conditions
as shown in Table 7.B.

Table 7.B

Status Reported in Word 1

Word

Bit

Explanation

1

00

Module is powered but has not received its first (configuration) block transfer.

The green LED is flashing.

01

One or more inputs are out of the range for which you configured the module.

02

Module updated its inputs before the processor read them. The RTSinterval

timed out before the processor read the data.

03

Not used

Word 1

(cont)

04

The module's ambient temperature is below 0

o

C. Temperature readings will

be inaccurate.

05

The module's ambient temperature is above 60

o

C. Temperature readings will

be inaccurate.

Troubleshooting with the

Indicators

Status Reported by the

Module