Chapter summary – Rockwell Automation 1771-IXE/D Thermocouple/Millivolt Input Module User Manual User Manual
Page 36
![background image](/manuals/579381/36/background.png)
4–8
Module Configuration
Publication 1771Ć6.5.130 Ć May 1999
Word
Description
Bits
Words 20
thru 27
Calibration words are a composite oftwo independent bytes for each
channel. Enter calibration data in signed magnitude binary only. The
most significant bit in each byte is the sign bit; set for negative, reset
for positive.
Use the high byte (bits 10-17) for offset correction, the low byte (bits
00-07) for gain correction for each channel. Use word 20 for channel
1 thru word 27 for channel 8.
Refer to Chapter 7 for calibration procedures.
Word 28
Auto-calibration request word - used to automatically calibrate
selected channels and save the calibration constants in EEPROM.
(Refer to Chapter 7.)
In this chapter you learned how to configure your module’s
hardware, condition your inputs and enter your data.
Chapter Summary