Module Configuration

Publication 1771Ć6.5.130 Ć May 1999

Word

Description

Bits

Words 20

thru 27

Calibration words are a composite oftwo independent bytes for each

channel. Enter calibration data in signed magnitude binary only. The

most significant bit in each byte is the sign bit; set for negative, reset

for positive.

Use the high byte (bits 10-17) for offset correction, the low byte (bits

00-07) for gain correction for each channel. Use word 20 for channel

1 thru word 27 for channel 8.

Refer to Chapter 7 for calibration procedures.

Word 28

Auto-calibration request word - used to automatically calibrate

selected channels and save the calibration constants in EEPROM.

(Refer to Chapter 7.)

In this chapter you learned how to configure your module’s
hardware, condition your inputs and enter your data.

Chapter Summary