Channel alarms calibration – Rockwell Automation 1771-IXE/D Thermocouple/Millivolt Input Module User Manual User Manual

Page 32

Advertising
background image

4–4

Module Configuration

Publication 1771Ć6.5.130 Ć May 1999

Table 4.C

Bit Settings for the Real Time Sample Mode

Decimal Bits

Octal Bits

15

17

14

16

13

15

12

14

11

13

Sample Time Period

0

0

0

0

0

RTS default(50ms)

0

0

0

0

1

100 ms

0

0

0

1

0

200 ms

0

0

0

1

1

300 ms

0

0

1

0

0

400 ms

0

0

1

0

1

500 ms

0

0

1

1

0

600 ms

0

0

1

1

1

700 ms

0

1

0

0

0

800 ms

0

1

0

0

1

900 ms

0

1

0

1

0

1.0 sec

0

1

1

1

1

1.5 sec

1

0

1

0

0

2.0 sec

1

1

0

0

1

2.5 sec

1

1

1

1

0

3.0 sec

1

1

1

1

1

3.1 sec

Important: Use decimally addressed bit locations for PLC–5
processors.

Each channel has an alarm enable bit, an alarm polarity bit, and high
and low alarm values associated with it. These bits and words are
explained in the bit/word definitions in Table 4.E.

You have the ability to calibrate this module using auto–calibration
or by manually setting the individual channel words. Words 20
through 27 in the configuration word (Table 4.E) are the calibration
words for channels 1 through 8 respectively. Calibration is explained
in chapter 6.

Channel Alarms

Calibration