6–3

Module Calibration

Publication 1771Ć6.5.130 Ć May 1999

Table 6.A

Write Block Transfer Word 28

Word

Bit

17 16 15 14 13 12 11 10 07 06 05 04 03

02

01

00

Inhibit Calibration

RequestedAuto-Calibration

Word28

8

7

6

5

4

3

2

1

Set these bits to 0

Requested

Save

Values

Requested

Gain Cal.

Requested

Offset Cal.

NOTE: Normally, all channels are calibrated simultaneously (bits
10–17 of word 28 are octal 0). To disable calibration on any
channel, set the corresponding bit 10 through 17 of word 28.

4. Queue block transfer reads (BTRs) to monitor for offset

calibration complete and any channels which may have not
calibrated successfully. Refer to Table 6.B.

Table 6.B

Read Block Transfer Word 13

Word

Bit

17 16 15 14 13 12 11 10

07

06

05 04 03

02

01

00

UncalibratedChannels

Auto-Calibration Status

Word13

8

7

6

5

4

3

2

1

Cal.

Fault

EEPROM

Fault

Not used

Save to

EEPROM

Complete

Gain Cal.

Complete

Offset Cal.

Complete

5. Proceed to Gain Calibration below.

Gain Calibration

Calibrating gain requires that you apply +100.000mV across each
input channel.

Normally all inputs are calibrated together. To calibrate the gain of
an input, proceed as follows:

1. Apply +100.000mV across each input channel as shown in

Figure 6.2.