Bit/word descriptions – Rockwell Automation 1771-IXE/D Thermocouple/Millivolt Input Module User Manual User Manual

Page 34

Advertising
background image

4–6

Module Configuration

Publication 1771Ć6.5.130 Ć May 1999

Bit/word descriptions of BTW file words 1 thru 3 (configuration), 4
thru 19 (channel alarm values), and 20 thru 27 (calibration values)
are presented in Table 4.E. Enter data into the BTW instruction after
entering the instruction into your ladder diagram program.

Table 4.E

Bit/Word Definitions for Thermocouple/Millivolt Input

Module

Word

Bits

Description

Word 1

bits 00-02

Input type codes for inputs 1 thru 8 (or 1 thru 4 if bit 06 is set to 1).

Tells the module what type of input device you connected to the

module.

Type

02

01

00

Millivolt input

0

0

0

"E" thermocouple

0

0

1

"J" thermocouple

0

1

0

"K" thermocouple

0

1

1

"T" thermocouple

1

0

0

"R" thermocouple

1

0

1

"S" thermocouple

1

1

0

1

1

1

bits 03-05

Input type codes for inputs 5 thru 8 (bit 06 must be set to 1). Tells the

module what type of input device you connected to inputs 5 thru 8.

Type

05

04

03

Millivolt input

0

0

0

"E" thermocouple

0

0

1

"J" thermocouple

0

1

0

"K" thermocouple

0

1

1

"T" thermocouple

1

0

0

"R" thermocouple

1

0

1

"S" thermocouple

1

1

0

1

1

1

bit 06

When set to 0 bits 00-02 define input type for all channels.

When set to 1 bits 00-02 defines input type for channels 1-4,

and bit 03-05 defines input type for channels 5-8.

bit 07

Not used (set to 0)

bit 10

Temperature scale bit, when set, reports temperature in

o

F; when

reset, in

o

C. The module ignores this bit for millivolt inputs.

Bit/Word Descriptions