Status reported in words 2 and 3 – Rockwell Automation 1771-IXE/D Thermocouple/Millivolt Input Module User Manual User Manual

Page 53

Advertising
background image

7–3

Troubleshooting

Publication 1771Ć6.5.130 Ć May 1999

Word

Explanation

Bit

06

Not used

07

EEPROM calibration constants could not be read. The module will continue to

operate but readings may be inaccurate.

10-17

Sign bits for each channel

Status Reported in Words 2 and 3

Design your program to monitor over/under range bits, and to take
appropriate action depending on your application requirements. You
may also want to monitor these bits while troubleshooting with your
industrial terminal.

Bits 00–07 and 10–17 each represent an input for channels 1–8,
respectively. For example, bit 04 represents input channel 5. The
module sets a bit (1) to indicate it has detected an out of range
condition. Refer to Table 7.C.

Table 7.C

Status Reported in Words 2 and 3

Word

Bit

Condition

2

00-07

Inputs underrange. Bit 00 is channel 1, bit 07 is channel 8. If input connections and

voltages are correct, this status may indicate failed channel communications with

the microprocessor. If all channels are underrange, this indicates a possible dc/dc

converter failure or a blown fuse.

10-17

Inputs overrange. Bit 10 is channel 1, bit 17 is channel 8. If input connections and

voltages are correct, this status may indicate a failed thermocouple functional

analog block (TC FAB).

3

00-07

Corresponding channel input value is below the alarm value that you entered for

that channel.

10-17

Corresponding channel input value has exceeded the alarm value that you entered

for that channel.