Rockwell Automation 1771-IXE/D Thermocouple/Millivolt Input Module User Manual User Manual

Page 69

Advertising
background image

Block Transfer (Mini–PLC–2 and PLC–2/20 Processors)

D–3

Publication 1771-6.5.130 Ć May 1999

The bits in the output image table control byte (bits 00 – 05) must be
programmed to specify a binary value equal to the number of words
to be transferred.

For example, NO TAG shows if your input module is set up to
transfer 6 words, you would set bits 01 and 02 of the lower image
table control byte. The binary equivalent of 6 words is 000110. You
would also set bit 07 when programming the module for block
transfer read operations. Bit 06 is used when block transfer write
operations are required.

Figure D.2

SettingBlock Length (Multiple GET Instructions only)

1

0 0

0 0 1

1

0

Data Address
Contains Module

Address in BCD

Output Image Table Control

Byte Contains Read
Enable Bit and Block

Length in Binary Code

010

012

017

027

030

1

2

0

Data Table

1

R

Control

Byte

Read 6 Words

from Module

Block Transfer

Read Enable Bit

For Block

Transfer Active
Operations Only

Output Image Table

12713

Number of

Words to

Transfer

Binary Bit Pattern

Lower Output Image Table Byte

05

04

03

02

01

00

Default

0

0

0

0

0

0

1

0

0

0

0

0

1

2

0

0

0

0

1

0

3

0

0

0

0

1

1

4

0

0

0

1

0

0

5

0

0

0

1

0

1

6

0

0

0

1

1

0

:

:

18

0

1

0

0

1

0

19

0

1

0

0

1

1