Rockwell Automation 1771-IXE/D Thermocouple/Millivolt Input Module User Manual User Manual

Page 74

Advertising
background image

Differences Between Series A, Series B, Series C and Series D Thermocouple/Millivolt

E–4

Publication 1771-6.5.130 Ć May 1999

The Series B module requires approximately 2 seconds to
execute initialization after power is applied.

The red LED will be turned on and the green LED
extinguished when the watchdog timer times out.

A type code of 111

2

will yield S type thermocouple.

Data format of 11

2

yields signed magnitude instead of 2’s

complement.

When the module is programmed for RTS = 0, and the PLC is
switched from run to program and back to run, an RTS timeout
is inhibited on the switch from program to run.

Allowable ambient temperature change to maintain accuracy is
0.5

o

C/min.

Series B, C and D have CE certification.