Performing autoćcalibration, Offset calibration – Rockwell Automation 1771-IXE/D Thermocouple/Millivolt Input Module User Manual User Manual

Page 42

Advertising
background image

6–2

Module Calibration

Publication 1771Ć6.5.130 Ć May 1999

Calibration of the module consists of applying 0.000mV across each
input channel for offset calibration, and +100.000mV across each
input channel for gain correction.

Offset Calibration

Normally all inputs are calibrated together. To calibrate the offset of
an input, proceed as follows:

1. Apply power to the module.

2. Connect shorting links, or apply 0.000mV across each input

channel on the 1771–WI field wiring arm as shown in Figure 6.1.

Figure 6.1

Shorting Inputs for Offset Calibration

1

Do not

use

18

Input 1 (+ lead)

17

Input 1 (- lead)

16

Input 2 (+ lead)

15

Input 2 (- lead)

14

Input 3 (+ lead)

13

Input 3 (- lead)

12

Input 4 (+ lead)

11

Input 4 (- lead)

10

Not Used

9

Not used

8

Input 5 (+ lead)

7

Input 5 (- lead)

6

Input 6 (+ lead)

5

Input 6 (- lead)

4

Input 7 (+ lead)

3

Input 7 (- lead)

2

Input 8 (+ lead)

1

Input 8 (- lead)

Terminal Identification

Terminal

Function

Wiring Arm

Cat. No. 1771-WI

18

17

16

1

15

14
13

12

11
10

9
8

7

6
5
4
3

2

Repeat for each channel

Apply

0.000mV

Short each input,

or apply 0.000mV

across each input

channel.

Shorting link.

10530-I

3. After the connections stabilize, request the offset calibration by

setting bit 00 in block transfer write word 28 and sending a block
transfer write (BTW) to the module. Refer to Table 6.A.

When the BTW is sent, all channels are calibrated to 0.000mV.

Performing

AutoĆCalibration