Programming Examples

B–4

Publication 1771-6.5.130 Ć May 1999

1.

Enter the following rung:

EN

BTW

BLOCK XFER WRITE

RACK:

GROUP:

MODULE:

CONTROL:

0

0

0

N7:0

DN

DATA FILE:

LENGTH:

CONTINUOUS:

N7:60

27

N

ER

Power Up Bit

N7:60 is the address of the BTW transfer file.

2.

Press [F8],[F5] and enter N7:60 to display the configuration
block. The industrial terminal screen should like Figure B.3.

Figure B.3

Sample PLC-5 Data File (Hexadecimal Data)

Address
N7:60
N7:70
N7:80

3

0040
0040
0000

5

0040
0040
0000

6

0085
0085

7

0040
0040

8

0085
0085

9

0040
0000

4

0085
0085
0000

2

00FF

0085
0000

1

00FF

0040
0000

0

5003
0085
0000

The above data file would configure the module as follow:

”K” thermocouples on all inputs

temperature scale of Celsius

output data in BCD format

real time sampling set to a 1 second scan rate

all channel alarms ON

all channel minimum alarm values set to –40

all channel maximum alarm values set to +85

all calibration values set to 0

3.

Enter the data corresponding to your bit selections and add alarm
and calibration values, if so desired.

4.

[ESC] returns you to the main menu.