Module Calibration

Publication 1771Ć6.5.130 Ć May 1999

For example, if the observed value was 17, enter –53 [(0 – 17) x
3.0933 = –53] in signed magnitude binary into the upper byte of
the calibration word for that channel. Enter 10110101 in bits
17–10 of word 20. The lower byte will remain zero at this time.

6. Repeat steps 3 through 5 for each of the remaining input

channels.

7. Initiate a write block transfer to send the corrections to the

module. The input value read by the processor should now be
0000 for all channels.

Setting Channel Gain Calibration

1. Now set the precision voltage source for +100.000 millivolts.

Allow sufficient time (at least 10 seconds) for the input filter and
voltage source to settle.

Figure 6.5

Applying 100.000mV for Gain Calibration

1

Do not

use

18

Input 1 (+ lead)

17

Input 1 (- lead)

16

Input 2 (+ lead)

15

Input 2 (- lead)

14

Input 3 (+ lead)

13

Input 3 (- lead)

12

Input 4 (+ lead)

11

Input 4 (- lead)

10

Not Used

9

Not used

8

Input 5 (+ lead)

7

Input 5 (- lead)

6

Input 6 (+ lead)

5

Input 6 (- lead)

4

Input 7 (+ lead)

3

Input 7 (- lead)

2

Input 8 (+ lead)

1

Input 8 (- lead)

Terminal Identification

Terminal

Function

Wiring Arm

Cat. No. 1771-WI

18

17

16

1

15

14
13

12

11
10

9
8

7

6
5
4
3

2

100.000mV

Apply

+

-