Rockwell Automation 1772-LV Mini-PLC - 2/15 Programmable Controller (Series B) Programming and Operations User Manual

Page 162

Advertising
background image

Special Programming Techniques

Chapter 11

11Ć15

Figure 11.8

24 Hour Clock

030

15

030

1.0

TON

Rung 1

PR 060

AC 000

030

15

031

CTU

Rung 2

PR 060

AC 000

031

15

032

CTU

Rung 3

PR 024

AC 000

031

15

031

CTR

Rung 4

PR 060

AC 000

032

15

032

CTR

Rung 5

PR 024

AC 000

Seconds

Minutes

Hours

Resets

the clock

A synopsis of the operation’s cycle is:

Rung 1: When the conditions are true the timer will start.

Rung 2: When AC=PR (accumulated value equals preset value) of the timer,
counter 031 increments.

Rung 3: When AC=PR of counter 031, counter 032 increments.

Rung 4: When AC=PR of counter 031, the -

031

(CTR)

- resets counter 031’s

accumulated value.

Rung 5: When AC=PR of counter 032, the -

032

(CTR)

- resets counter 032’s

accumulated value.