Fundamental Instruction Set

Chapter 5

5Ć16

Less Than

Symbol: -|<|-

Purpose: Compares the data in your specified address with the data stored at
another address in memory. It determines the rung condition.

Syntax: Programmed after the get instruction in the condition side of the ladder
diagram rung (Figure 5.7).

Function: The rung condition becomes:

True

If the get value is less than the reference values stored in the less than

instruction.

False

If the get value is not less than the less than value.

Figure 5.7

Less Than Comparison

120

01

010

00

030

YYY

G

037

654

<

Reference Value

When YYY < 654, GET/LES comparison is true and 01000 is energized.

Get Byte

Symbol: -|B|-

Purpose: Accesses 1 byte (instead of 1 word) from one word location of the
data table.

Syntax: Can be programmed with a limit test instruction located at the
condition area of the ladder diagram (Figure 5.8). The data is shown in octal
form.

Function: Used with a put instruction to transfer either the upper or lower byte
to the lower byte of the put address.

Figure 5.8

Get Byte/Limit Test Comparison

120

06

010

00

0451

YYY

G

050

L

Reference Value

When 170 <YYY <200, comparison is true and 01005 is energized.

200

170

Limit Test

Symbol: -|L|-

Purpose: Checks to see if a byte value is between two reference byte values in
the limit test instruction.

Syntax: Programmed with a get byte instruction located at the condition area
of the ladder diagram (Figure 5.8).