Rockwell Automation 1772-LV Mini-PLC - 2/15 Programmable Controller (Series B) Programming and Operations User Manual

Page 190

Advertising
background image

Quick Reference Section

Appendix A

AĆ21

Table A.O

Troubleshooting Aids

Function

Key Sequence

Mode

Description

Bit monitor

[SEARCH]

[5][3]

[Address]

Any

Displays the on/off status of all 16 bits at specified

word address and corresponding force conditions if

they exist.

[

] or [

]

Displays the status of 16 new bits at the next lowest

or highest word address, respectively.

Bit manipulation

[SEARCH]

[5][3]

Test or

Run/Program

Displays the on/off status of all 16 bits at specified

word address and corresponding force conditions if

they exist.

[<-] or [->]

[1] or [0]

See FORCING below

Moves cursor to the bit to be changed.

Enter a 1 to set bit on or a 0 to reset a bit.

Forcing or removing forces from input bits or output

devices.

Either of above

[CANCEL

COMMAND]

To terminate.

Force On

[FORCE ON]

[INSERT]

Test or

Run/Program

Position the cursor on the image table bit to be

forced on and press the key sequence. The input bit

or output device will be forced on.

Removing a Force On

[FORCE ON]

[REMOVE]

Test or

Run/Program

Position the cursor on the image table bit whose

force on is to be removed and press the key

sequence.

Removing all Force On

[FORCE ON]

[CLEAR MEMORY]

Test or

Run/Program

Position cursor anywhere in program and press key

sequence.

Force Off

[FORCE OFF]

[INSERT]

Test or

Run/Program

Position the cursor on the image table bit to be

forced off and press the key sequence. The input bit

or output device will be forced off.

Removing a Force Off

[FORCE OFF]

[REMOVE]

Test or

Run/Program

Position the cursor on the image table bits whose

force off is to be removed and press the key

sequence.

Removing all Force Off

[FORCE OFF]

[CLEAR MEMORY

Test or

Run/Program

Position the cursor anywhere in program and press

key sequence.

Forced address display

[SEARCH]

[FORCE ON]

or

[SEARCH]

[FORCE OFF]

Any

Displays a list of the bit addresses that are forced

on and forced off. The [SHIFT] [ ] and [SHIFT] [ ]

keys can be used to display addition forces.

[CANCEL

COMMAND]

To terminate.

Inserting a temporary end

instruction

[INSERT]

[ ] [T.END]

or

Program

Position the cursor on the on the instruction that will

follow the temporary end instruction. The remaining

rungs, although displayed and accessible, are not

scanned.

Advertising