Fundamental Instruction Set

Chapter 5

5Ć8

The rung below achieves the same result, but avoids nested branching:

110

00

010

00

110

10

110

11

110

12

110

13

110

11

Section C

Timers and Counters

Timer and counter instructions are output instructions internal to the controller.
They provide many of the capabilities available with timing relays and solid
state timing/counting devices. Usually conditioned by examine instructions,
timers and counters keep track of timed intervals or counted events according to
the logic continuity of the rung. You can program a maximum of 488 internal
timers and/or counters.

Each timer or counter instruction has two 3-digit values. Each value requires
one word of data table memory. These 3-digit values are:

Accumulated

Value

(AC)

Storage: Begins at word address 030.

Function: Timers - number of elapsed timed intervals.
Counters - number of counted events.
Both - upper 4 its of accumulated word (14-17) are the status bits.

Preset

Value

(PR)

Storage: Always 100

8

words greater than its corresponding AC value.

Function: Denotes the number of timed intervals or events to be counted.
When the accumulated value equals the preset value, AC=PR, a status bit is
set and can be examined to turn an output device on or off.

Introduction

A timer counts elapsed time-base intervals and store this count in the
accumulated value word. Timer instructions have three time bases: 1.0 second,
0.1 second, or 0.01 second.

Introduction

Timer/Counter Theory

Timer Instructions