Mini-PLC-2/15 System:

An Overview

Chapter 3

3Ć2

Figure 3.1

MiniĆPLCĆ2/15 Programmable Controller

18404

System Status Indicators

These indicators are located on the front panel of the controller and power
supply. They indicate error conditions and are labeled as:

Processor

Indicator:

red

State: On indicates that the processor is unable to scan the program and I/O.

Off indicates no error.

Response: The processor will cease to operate and outputs will either be
disabled or held in their last state in accordance with the I/O chassis switch
setting.

Memory

Indicator: Red

State: On indicates errors in either:

Memory

data

Parity
EPROM

Off indicates no error.

Blinking indicates an error in EPROM.

Response: The processor will halt all operations and disable all outputs.