13.Test your Ladder Program. Do the following:

A. Press pushbutton #0 for at least 10 seconds. During the first 10

seconds, output #0 turns ON and #1 stays OFF. The following display
appears:

<END>

F1

F2

F3

F4

F5

2.3.0.0.*

] [

(

TON

)

] [

( )

] [

( )

These bit instructions become bold.

RUN

MODE

FORCE

SEARCH

EDT_DAT

B. After 10 seconds, output #0 turns OFF and output #1 turns ON. The

following screen appears:

<END>

F1

F2

F3

F4

F5

2.3.0.0.*

] [

(

TON

)

] [

( )

] [

( )

These bit instructions become bold.

RUN

MODE

FORCE

SEARCH

EDT_DAT

C. Release pushbutton #0; the timer resets and both outputs #0 and #1

turn OFF.

D. Place the cursor on the

TON

instruction (press the

[

]

key twice).

Press

[ZOOM]

. The following screen appears:

ZOOM on TON –(TON)–
NAME:

TIMER ON DELAY

TIMER:

T4:0

TIME BASE .01 SEC

PRESET:

1000

ACCUM:

0
EN

TT

DN

0

0

0

F1

F2

F3

F4

F5

EDT_DAT

2.0.0.0.2

The accumulator value changes
In step (e).

Notice that the values for EN,
TT, and DN also change.

E. Repeat steps A, B and C. Watch the timer accumulator value change.