System led status – Rockwell Automation 1747-PTxx Getting Started Guide for HHT User Manual

Page 60

Advertising
background image

Appendix B
Troubleshooting Errors

Getting Started Guide

for HHT

B–3

The System LEDs are located at different places on the modular system and
the SLC fixed controller. Refer to the Installation and Operation manual for
more information on system LED status. See the figure and table below:

Modular System

SLC 500 Fixed Controller

BATTERY LOW

FORCED I/O

CPU FAULT

PC RUN

BATTERY LOW

FORCED I/O

CPU FAULT

PC RUN

POWER

POWER

Processor LED

Status of LED

Cause

Corrective Action

POWER

Off

No DC power to backplane

Verify line power within range. Verify
wiring and grounding. Check power
supply fuse. For modular system,
verify power supply jumper is posi-
tioned correctly and that the power
supply has been sized properly for
loading in the rack.

CPU FAULT

Steady

Bad CPU or firmware improperly
installed

Verify that position of notch in proces-
sor firmware chip matches processor
board diagram. See corrective action
for Power LED.

CPU FAULT

Flashing

Processor major fault

Correct the problem based on the er-
ror message. First clear the fault.
Then press and return processor to
RUN mode. See processor error
codes.

BATTERY LOW

Steady

Battery voltage fallen below thresh-
old to retain RAM memory; or no
battery present; or LED jumper is
missing

Replace 1747–BA and do not remove
processor power; or add 1747–BA to
retain RAM memory; or add LED
jumper to prevent the LED from
lighting.

System LED Status