Start–up and Troubleshooting

Chapter 9

9-8

Figure 9.3
REMOTE/LOCAL FAULT Bit Significance

AC FUSE

PLC

2/20

Local Fault
Possible Sources:

Disconnected data highway cable

Power off at receiving station
interface module

Unused remote staiton no. address

Station interface moduel at local
or remote station has disconnected
itself as a result of link monitoring

Automatic timeout at sending
station


AC FUSE

PLC
2/20

Remote Fault

Possible Sources:

Remote station processor
in program load (or prog)
mode

Command not executed due to
module switch setting at
receiving station

Fault at remote station processor

Power off at remote station processor

Disconnected data highway/processor cable

Error detected in communication zone of
program at remote station proccessor




Processor

Processor

Receiving (Remote) Station

10866-I

Sending
Station

ERROR CODE Storage Word

The ERROR CODE storage word is especially useful for station start-up.
The codes displayed in the lower 2 digits of the ERROR CODE word may
indicate an error in programming, switch-setting, or certain other
conditions that prevent normal communication adapter module operation.

The ERROR CODE storage word is addressed by the second GET
instruction in the header rung (Refer to Figure 9.4.) This is the first rung
of the communication zone of program.