Rockwell Automation 1771-KA2 Communication Adapter Module User Manual

Page 90

Advertising
background image

Command Initiation, Execution, and
Monitoring

Chapter 7

7-18

to detect such a condition; the simplest of these methods uses an
ON-DELAY timer. Figure 7.9 shows typical rungs that can be
programmed for this purpose.

Figure 7.9
Typical User-Programmed Timeout

033 12

/

Remote Fault

TON

060

0.1

032 12

Start

01002

060 15

Timed Bit

Indicator

Output

032 02

/

PR 100
AC 000

033 02

/

Local Fault

Done

In the first rung of this figure, timer 060 times the interval between the
setting of the START bit for a command and the DONE, LOCAL FAULT,
or REMOTE FAULT response of the module. If no response is received
within the preset interval of this timer, here 10 seconds, a fault may be
indicated and bit 06015 set ON. The second rung examines this bit to turn
on a warning indicator. Depending on the individual application, this bit
could also be used to enable or disable various parts of the program.

The preset value of this programmed TON instruction is not critical. For
this type of backup monitoring, the programmed preset must exceed the
timeout preset interval entered as a code in the header rung. (Remember
that the automatic timeout of the module gives a LOCAL FAULT
response to a command, which would indicate normal module/processor
communication, but faulted communication with some other station.)

As with automatic timeout preset monitoring, a user-programmed timeout
is useful as a backup to the other monitoring functions of the

Advertising