Rockwell Automation 1771-KA2 Communication Adapter Module User Manual

Page 18

Advertising
background image

Station Hardware

Chapter 2

2-8

Module Specification Summary

Table 2.A lists operating specifications for a 1771-KA2 module.

Table 2.A
Operating Specifications

Function

Interface entire PLC-2 family
programmable controller to the Data
Highway

Compatible Power Supplies

System power supply (cat. no. 1771-P1)

Auxiliary power supply (cat. no. 1772-P2)

Location

Bulletin 1771 I/O Chassis (any slot
except furthest left)

System power supply module (cat. no.
1772-P1, series B or later)

Communication Channels

To Data Highway

To programming terminal or second
module in daisy chain

To processor or first module in daisy
chain

Auxiliary power supply (cat. no. 1772-P2
series B or later)

Power supply module 1771-P3

Power supply module 1771-P4

Power supply module 1771-P5

Communication Rates

To Data Highway: 57.6k baud
(Recommended)

To programming terminal or second
module: 9.6k buad

To processor: 91.2k baud for
processor (except PLC-2, cat. no.
1772-LR); 9.6k baud for first
communication module or PLC-2-
family processor.

Ambient Temperature Rating

32

o

to 140

o

F (0

o

to 60

o

C) (operational)

-40

o

to 185

o

F (-40

o

- 85

o

C) (storage)

Humidity Rating

5% to 95% (without condensation)

Keying

Module slotted for I/O chassis keying
band positioning.

Positions 4-6, 22-24

Power Supply Requirement

+5V DC at 1.2A (max.)

This manual uses the term “processor” as a general term for any of the
PLC-2 family processors. Individual processors are specified only when
some distinction must be made.

The normal operating sequence of the station processor is not changed by
a communication adapter module, that is, the processor carries out its scan
of input and output modules and execution of the user program as though
the communication adapter module weren’t there.

Processor

Advertising