Chapter 5

5-9

The START bit is controlled by the program. This allows a command to
be initiated only when necessary. (Programming methods for START bit
control are given in chapter 7.)

Command Code

The second element in a command rung, the command code, identifies the
following:

Remote station number
Priority status of the command (priority or normal)
Type of command

NOTE: The command code uses the address of an EXAMINE ON
instruction, but does not examine or control any bit in the data table of the
local station processor.

Figure 5.5 shows the coding for this rung element.

Word Command Format

When the command code specifies a protected write, read, or unprotected
write command, use the format shown in Figure 5.6.

Figure 5.6
Word Command Format

027 07

032 10

020 00

AAA

G

BBB

G

CCC

G

AAA

Legend

BBB

CCC

Start
Bit

Command
Code

Local Station Processor
Data Table Boundaries

Remote Station Processor
Data Table Address

Beginning word address of remote station processor for write/read operation

Beginning Word Address of local station processor for write/read operation

Ending Word Address at local station processor for write/read operation