Communication Zone Rungs

Chapter 5

5-11

Figure 5.7
Bit Command Format

027 07

EEEEE

FFFFF

/

GGGGG

/

HHH HH

IIIII

/

JJJ JJ

–] [–

Legend:

Branch Start

(If Needed)

–] / [–

EEEEE

Start
Bit

Command
Code

FFFFF

Set bit EEEEE in remote station data table on

Set bit FFFFF in remote station data table off

.

.

.

/

Area May Contain Any Legal
Combination Of These Instructions:

This format uses EXAMINE elements that address bits in the remote
station processor. These elements control remote station data table bits as
follows:

-] [- EXAMINE ON - This rung element instructs the remote station

communication adapter module to turn the addressed bit on.

-]/[- EXAMINE OFF - This rung element instructs the remote station

communication adapter module to turn the addressed bit off.

Program these elements immediately after the command code. Any
combination of these elements may make up this type of command rung.
Where necessary, BRANCH START instructions and a BRANCH END
instruction can be used to fit these elements into the display area of the
programming terminal. For practical reasons, do not exceed this display
area. Multiple rungs of this type can be used as necessary.

The delimiter rung ends the communication zone of program. With
PLC-2 family processors, this rung always has the format shown in
Figure 5.8.

Delimiter Rung