Start–up and Troubleshooting

Chapter 9

9-22

Figure 9.8
Disconnecting a Station

Trunkline In

Trunkline Out

Ground Wire

#12 Ga. to Earth Ground

Dropline Cable

15–Pin Connector

To Data Highway Module

Cable

Trunkline

Dropline

1

6

3

8

7

2

Shield

Clear

Blue

Cable Wiring

(Green)

Pin 6 Blue
Pin 7 Shield
Pin 8 Clear

1

4

3

2

Notes:

Twist trunkline wires of same color before securing to screw–clamp terminals 1, 2 and 3.

For dropline cable ten feet or less, isolate the dropline shield from the enclosure.

For dropline cables greater than ten feet, attach the dropline drain wire to terminal 7.

1770–SC
Station Connector

Tee Connector

Trunkline

Dropline

Tee Connector

Remove trunkline
segments, then
connect them to
each other. Tee
connector is free.

Trunkline Segments

Segment

Trunkline Segment

Before

After

1

2 3

11

3

2

4

When the station is first or last on a trunkline, attach a 150W resistor to terminals 1 and 3.