Rockwell Automation 1771-KA2 Communication Adapter Module User Manual

Page 85

Advertising
background image

Command Initiation, Execution, and
Monitoring

Chapter 7

7-13

Figure 7.7
FAULT Bit Diagnostic Rungs (Multiple Commands Example)

055 01

/

Remote Fault Status

TOF

030

0.1

055 00

/

Local Fault

Status

010 00

030 15

Timed Bit

Indicator

Output

Rung 1

Rung 3

Rung 4

055 00

033 07

/

033 06

/

033 05

/

033 04

/

033 03

/

033 02

/

033 01

/

033 00

/

Status

Local Fault

Rung 2

055 01

033 17

/

033 16

/

033 15

/

033 14

/

033 13

/

033 12

/

033 11

/

033 10

/

Status

Remote Fault

PR 020
AC 000

This example shows the FAULT bit monitoring for 8 commands. The 8
LOCAL FAULT bits are monitored in rung 1. As long as all 8 bits are
OFF, status bit 05500 remains ON. However, should any LOCAL FAULT
bit be ON, status bit 05500 is de-energized. In rung 2, the 8 REMOTE
FAULT bits are monitored in the same manner, to control status bit 05501.

The status bits controlled by rungs 1 and 2 are, in turn, used to control an
OFF-DELAY timer in rung 3. The OFF-DELAY timer begins to time
when either of the status bits goes from OFF to ON, that is, when rung
conditions go from TRUE to FALSE. Bit 03015, the timed bit of the
timer, controls the output indicator. As soon as the conditions of the timer
in rung 3 are TRUE, this bit is set ON causing the indicator to be
energized. Once ON, this bit remains on as long as the timer is timing,
that is, for at least as long as the preset interval. In the example of
Figure 7.7, this preset is set at 2 seconds. This value is not critical but
should exceed 0.5 seconds for practical purposes.

Advertising