Station Interfacing

Chapter 8

8-7

Table 8.A
Diagnostic Command Summary

Command

Function

Diagnostic loop

Echoes transmitted data back in reply message

Diagnostic read

Copies up to 245 bytes of data from module
memory

Diagnostic counters
reset

Resets all diagnostic error counters n the module

Diagnostic status

Allows access to 28 bytes of processor and
module status information

Other commands are available for communication with other processors,
but will return an error code if sent to a PLC-2 family processor.

Indications of Upload, Download (Earlier revisions)

If you are using a revision of the 1771-KA2 module before revision D, or
a revision of the 1770-T3 terminal before revision G, and are uploading or
downloading, the 1770-T3 terminal will:

display a mode select menu and a communication fault message
clear all force instructions

(Later Revisions)

When you connect a 1770-T3 terminal (revision G or later) to a
1771-KA2 module (series A, revision D or later) and perform program
uploads with the 1770-T3 terminal in the PLC-2 mode, the terminal does
the following:

Uploads

1.

Displays the prompt:
UPLOAD IN PROGRESS - PLEASE WAIT FOR COMPLETION

2.

disables the PLC-2 mode

3.

displays the prompt:
UPLOAD COMPLETED - PRESS ANY KEY TO CONTINUE

4.

re-enables the PLC-2 mode and forces are maintained after you press
any key