Status Words

Chapter 6

6-3

As Figure 6.1 shows, the selection of a START bit in the program not only
causes a corresponding DONE bit to be controlled in the same word, but
also causes REMOTE and LOCAL FAULT bits to be controlled in the
next data table word. A REMOTE FAULT and LOCAL FAULT bit are
controlled for each command. For a command, the position of each of
these FAULT bits within their respective bytes corresponds directly to the
position of START and DONE bits for that command.

The KA2 controls REMOTE and LOCAL FAULT bits. The module sets a
FAULT bit ON when a command cannot be executed due to a
hardware-related fault either between stations or between the remote
station communication adapter module and its station processor.
Figure 6.2 summarizes the significance of these bits.

Figure 6.2
REMOTE/LOCAL FAULT Bit Significance

AC FUSE

PLC

2/20

Local Fault
Possible Sources:

Disconnected data highway cable

Power off at receiving station
interface module

Unused remote staiton no. address

Station interface moduel at local
or remote station has disconnected
itself as a result of link monitoring

Automatic timeout at sending
station


AC FUSE

PLC
2/20

Remote Fault

Possible Sources:

Remote station processor
in program load (or prog)
mode

Command not executed due to
module switch setting at
receiving station

Fault at remote station processor

Power off at remote station processor

Disconnected data highway/processor cable

Error detected in communication zone of
program at remote station proccessor




Processor

Processor

Receiving (Remote) Station

10866-I

Sending
Station

REMOTE/LOCAL FAULT Word