Communication zone rungs chapter 5 – Rockwell Automation 1771-KA2 Communication Adapter Module User Manual

Page 58

Advertising
background image

Communication Zone Rungs

Chapter 5

5-6

Figure 5.3
Memory Access Example

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙ

Memory Access
Boundaries in
Local Station
Data Table

Remote
Station No.

Starting
Address

Ending
Address

Branch Start
Instruction
(Required)

a) Memory Access Branch

b) Local Station Processor

Data Table

010

020

023

G

G

G

Words
020

023

Area
Accessible to
Protected Commands
From Remote
Station No. 010

Branch End
Instruction
(Required)

Figure 5.4 shows a memory access rung with multiple branches. This
rung lists the remote station that may control specific data table words
with protected commands, as follows:

Station no. 020 can control words 070-076
Station no. 017 can control words 063-065 and word 022
Station no. 010 can control words 060-062

As shown in Figure 5.4, a single remote station processor may be
identified in more than one memory access rung branch.

Figure 5.4
Memory Access Rung (typical)

020

[ G ]

070

[ G ]

076

[ G ]

017

[ G ]

022

[ G ]

022

[ G ]

(

02707

)

017

[ G ]

063

[ G ]

065

[ G ]

010

[ G ]

060

[ G ]

062

[ G ]

Use Branch End
Instructions
as Needed

One Branch End
Instruction Must
Precede Output
Instruction

Branch
Start
Instructions
Begin
Each
Branch

000

000

000

000

000

000

000

000

000

000

000

000

Advertising