Commands

Chapter 4

4-14

address code 010

addresses the first controller - controller 1 - while

address code 011

addresses the second controller - controller 2.

A PLC-4 Microtrol uses a decimal addressing scheme (Table 4.A). The
PLC-2 family of programmable controllers use an octal addressing
scheme. Thus, you must convert the PLC-4 Microtrol’s decimal addresses
to octal.

Address codes are divided into four sets:

1.

store words

2.

input, output, and flag words

3.

input, output and flag area

4.

timer/counter words

When using these address codes, observe these restrictions:

1.

Do not address more than one set at a time. For example, if you want
to read both the store and the input words of controller 1, send one
command to read the store area, and a second command to read the
input words.

2.

Do not address more than one controller at a time. For example, if
you want to read the store area of both controller 1 and controller 2,
send two separate read commands.

3.

Do not send a command to a controller that is in program mode. A
controller in program mode is not an active member of the loop,
because its data table is not being updated.