Rockwell Automation 1771-KA2 Communication Adapter Module User Manual

Page 48

Advertising
background image

Commands

Chapter 4

4-12

The addressing scheme is summarized in this chart:

Table 4.A
Internal Addressing of a PLC-4 Microtrol Controller

Type of

Address

Controller

I.D.

Bit

Address Range

I=Input

1-8

01-20

O=Output

1-8

01-12

X=Flags

1-8

01-32

(1)

S=Stores

1-8

01-99

Type of

Address

Controller

I.D.

Timer/Counter

Number

Bit

Description

T = Timer

1-8

01-32

15 - Timer Clock

16 - Enable

31 - Timer Timing

32 - Done

C = Counter

1-8

01-32

15 - Count -Down Enable

16 - Count-Up Enable

31 - Overflow Underflow

32 - Done

(1) Flag bits 31 and 32 have a special significance. See the PLC-4 Microtrol Product Guide

(publication 1773-800).

The memory map for a PLC-4 Microtrol controller, ID #1, shown in
Figure 4.4, includes data on inputs, outputs and flags of each active
controller on the loop.

Each member of the PLC-4 Microtrol loop, including the interface
module, shares the status of the input, output, and flag bits for each
controller on the loop. This becomes significant when you want to
determine response time.

Each time you enter a non-privileged command, you must enter an
address code. This becomes significant when you want to determine
response time.