Publication 1794-6.5.11 - September 2011

Overview of the Frequency Input Module 9

Normal Mode Frequency Determination, at Least Two Pulses
in Sampling Time

If only one pulse occurs within the sampling window, when the sample time
has expired, the window is extended to 2 s to allow for a second pulse to occur.
As soon as a second pulse occurs, the frequency is calculated and the
procedures starts over. If no second pulse is detected, zero frequency is
reported and a Missing Pulse Alarm is generated. The following figure depicts
this scenario.

Normal Mode, Only One Pulse in Sampling Time,
Sampling Time Extended

Missing pulse alarm would be
reported after 2 s, if no pulse occurs

Frequency reported
at end sampling time

Pulses counted

T2 - T1

pulses counted

First pulse in window,
T1 time stored

Last pulse in window

T2, update as each
pulse occurs

Minimum sampling time

Frequency input

pulses

45340

=

45341

Frequency reported at

first pulse in extended Time

2 - 1

T2 - T1

=

Missing pulse alarm is reported after 2 s, if no pulse occurs

Minimum
sampling time

Frequency input
pulses

2 = pulses counted

First pulse in window,
T1 time stored

First pulse after
window extended,
T2 time stored

Sampling time
extended to 2 s