Publication 1794-6.5.11 - September 2011

Program Your Module with PLC Processors 67

PLC-5 Family Processor

Block transfer instructions with the PLC-5 processor use a control file and a
data file. The block transfer control file contains the data table section for
module location, the address of the block transfer data file and other related
data. The block transfer data file stores data that you want transferred to the
module (when programming a BTW) or from the module (when programming
a BTR).

The programming terminal prompts you to create a control file when a block
transfer instruction is being programmed. A different block transfer control
file is used for the read and write instructions for your module.

13

U

IJ2 BTR

Error Bit

B17:0

EN

BTR

BLOCK TRANSFER READ
Rack
Group
Slot

Data File

3
2
0

N18:101

Length

Control

0

B17:0

EN

BTW

BLOCK TRANSFER WRITE
Rack
Group
Slot

Data

3
2
0

N18:1

DN

Length

Control

0

B17:0

5

B17:0

B17:0

15

ER

DN

ER

Rung M:0
The IJ2 module is located in rack 3, I/O group 2, slot 0. The control file is a 10 word file

starting at B17:0 that is shared by the BTR/BTW. The data obtained by the PLC3 processor is

placed in memory starting at location N18:101, and with the default length of 0, is 7 words long.

IJ2 BTR

Done Bit

IJ2 BTR/BTW

Control Block

The IJ2 module is located in rack 3, I/O group 2, slot 0. The control file is a 10 word file

starting at B17:0 that is shared by the BTR/BTW. The data sent by the PLC-3 processor to the

IJ2 module is from PLC memory starting at N18:1, and with the default length of 0,

is 8 words long.

13

IJ2 BTR

Error Bit

B17:0

IJ2 BTW

Done Bit

IJ2 BTR/BTW

Control Block

3

B17:0

3

B17:0

U

IJ2 BTW

Error Bit

IJ2 BTW

Error Bit

PLC-3 Processor
Program Example