Specifications 57

Power dissipation, max

4.6W @ 31.2V DC

Thermal dissipation, max

15.6 BTU/hr @ 31.2V DC

Indicators (field side driven,
logic side indication)

1 green/red power/status indicator
4 yellow status indicators (Freq 0, 1, Gate 0, 1)
4 red wire-off indicators (Freq 0, 1, Gate 0, 1)
2 yellow status indicators (Out 0, Out 1) – logic side

Keyswitch position

1

Wire size

Determined by installed terminal base

Wiring category

(1)

2 – on signal ports
3 – on power ports

Wire type

Shielded on signal ports

Terminal screw torque

Determined by installed terminal base

Enclosure type rating

None (open-style)

North American temp code

T4A

IEC temp code

T4

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication

1770-4.1

.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F) – 1794-IJ2 and 1794-IJ2K
-20…70 °C (-4…158 °F) – 1794-IJ2XT

Temperature,
non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating
Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)