Appendix a, A – specifications, What this appendix contains – Rockwell Automation 1794-IJ2XT FLEX I/O Frequency Input Modules User Manual User Manual

Page 65: Specifications, Appendix

Advertising
background image

55

Publication 1794-6.5.11 - September 2011

Appendix

A

Specifications

What This Appendix
Contains

This appendix contains the frequency accuracy and general specifications of
the Frequency Input module (1794-IJ2, 1794-IJ2K, and 1794-IJ2XT).

Input Specifications

Attribute

Value

Number of input channels

2

Number of inputs per
channel

2 – Frequency and Gate
(gate used to establish direction)

Input frequency, max

32 kHz

Frequency value, max

32,767 Hz or 3,276.7 Hz (dependent on range)

Input pulse width

20

μ

s

Resolution and accuracy

See table,

Resolution and Accuracy

, on page 24

On-state voltage, min

10V (24V IEC+1 proximity, encoder input or switch inputs)

On-state voltage, nom
(selected by terminal base
connections)

50 mV AC, 28V AC peak – Extended magnetic pickup
500 mV AC, 28V AC peak – Magnetic pickup
< 3V – Vortex flowmeter low range
> 6V – Vortex flowmeter high range
24V DC IEC+1 proximity or encoder input
24V DC Contact switch input

On-state voltage, max

Limited to isolated 24V DC power supply

On-state current

min
nom
max

2.0 mA
9.0 mA
10.0 mA

Off-state current

<1.5mA into 24V DC IEC+ terminal

Off-state voltage, max

5.0V DC on 24V DC IEC+1 terminal

Wire-off detection

0.4 mA for proximity, encoder or contact switch with
50 k

Ω

shunt resistor

Frequency input impedance

>5 K

Ω

for 50 mV Extended magnetic pickup

>5 K

Ω

for 500 mV Magnetic pickup

>10 K

Ω

for 3V Vortex flowmeter low range

>10 K

Ω

for 6V Vortex flowmeter high range

>2.5 K

Ω

for 24V DC IEC+1 proximity or encoder input

>2.5 K

Ω

for 24V DC Contact switch input

Gate input impedance

>5 K

Ω

for 50 mV Extended magnetic pickup

>5 K

Ω

for 500 mV Magnetic pickup

>2.5 K

Ω

for 24V DC IEC+1 proximity or encoder input

>2.5 K

Ω

for 24V DC Contact switch input