Rockwell Automation 1794-IJ2XT FLEX I/O Frequency Input Modules User Manual User Manual

Page 56

Advertising
background image

Publication 1794-6.5.11 - September 2011

46 Read and Write Configuration Maps for the FLEX I/O Module

Word 6

Bits 00…01

Wire-Off/Missing Pulse fault select (channel 1) – Sets the mode for 24V DC IEC 1+ Wire
Off Input Detection and Missing Pulse Detection result for any input (Frequency or Gate).
The Maximum Frequency is determined by Frequency Range bit and the Maximum
Frequency value, and the Minimum Frequency is determined by Frequency Range bit.
The Wire Off detect time (in mode 1, 2, and 3) is 2 seconds maximum.

Bit

01

00

Channel wire-off or missing pulse fault mode

0

0

Disabled

0

1

Alarm only (frequency unchanged)

1

0

Alarm and force frequency to maximum frequency value (32767 or
3276.7 or maximum frequency value, 0).

1

1

Alarm and force frequency to minimum frequency value (0 or 0.0).

Bits 02…03

Missing pulse delay multiplier bits (channel 1) – Specifies the number of Missing Pulse
Alarms periods (Minimum Frequency Sampling Times) which will be tolerated before the
alarm is actually generated, if enabled. (Used to defeat the Missing Pulse Alarm during
a system startup.)

Default = 0 – No multiplier; alarm generated immediately (normal mode with 2 s
extension delay)

Bit

03

02

Alarm periods before alarm generated

0

0

No multiplier; alarm generated immediately (normal mode with 2 s
extension delay)

0

1

2 sample periods + 2 s delay before alarm

1

0

8 sample periods + 2 s delay before alarm

1

1

32 sample periods + 2 s delay before alarm

Bit 04

Frequency or Acceleration Alarm Select (channel 1) – Determines if the value in the
Maximum Frequency or Acceleration write word is a Frequency (actual or scaled) or
Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.

0 = Frequency alarm
1 = Acceleration alarm
Default = 0 – frequency alarm

Bits 05…06

Acceleration Calculation Time (channel 1) – Specifies the number of Frequency Sample
Times over which the module calculates acceleration.

Default = 0 – Rolling Average (previous 4 samples)

Bit

06

05

Acceleration Calculation Time in Frequency Sample Times

0

0

Rolling Average (previous 4 samples)

0

1

8

1

0

16

1

1

32

Bit/Word Definitions for the Block Transfer Write Words

Word

Bit

Definition

Advertising