Publication 1794-6.5.11 - September 2011

Read and Write Configuration Maps for the FLEX I/O Module 43

Word 3

Bits 00…01

Wire-Off/Missing Pulse fault select mode (channel 0) – Sets the mode for 24V DC IEC 1+
Wire Off Input Detection and Missing Pulse Detection result for any input (Frequency or
Gate). The Maximum Frequency is determined by Frequency Range bit and the
Maximum Frequency value, and the Minimum Frequency is determined by Frequency
Range bit. The Wire Off detect time (in mode 1, 2, & 3) is 2 seconds maximum.

Bit

01

00

Channel wire-off/missing pulse detection mode

0

0

Disabled

0

1

Alarm only (frequency unchanged)

1

0

Alarm and force frequency to maximum frequency value
(32767 or 3276.7 or maximum frequency value, 0).

1

1

Alarm and force frequency to minimum frequency value (0 or 0.0).

Bits 02…03

Missing pulse delay multiplier bits (channel 0) – Specifies the number of Missing Pulse
Alarms periods (Minimum Frequency Sampling Times) which is permitted before the
alarm is raised, if enabled. Used to defeat the Missing Pulse Alarm during a system
startup.

Default = 0 – No multiplier; alarm generated immediately (normal mode with 2 s
extension delay)

Bit

03

02

Alarm periods before alarm generated

0

0

No multiplier; alarm generated immediately (normal mode with 2 s
extension delay)

0

1

2 sample periods + 2 s delay before alarm

1

0

8 sample periods + 2 s delay before alarm

1

1

32 sample periods + 2 s delay before alarm

Bit 04

Frequency or Acceleration Alarm Select (channel 0) – Determines if the value in the
Maximum Frequency or Acceleration write word is a Frequency (actual or scaled) or
Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.

0 = Frequency alarm
1 = Acceleration alarm
Default = 0 – frequency alarm

Bits 05…06

Acceleration Calculation Time (channel 0) – Specifies the number of Frequency Sample
Times over which the module calculates acceleration.

Default = 0 – Rolling Average (previous 4 samples)

Bit

06

05

Acceleration Calculation Time in Frequency Sample Times

0

0

Rolling Average (previous 4 samples)

0

1

8

1

0

16

1

1

32

Bit 07

Initiate Startup Select (channel 0) – Alerts a channel that if process start up is in
progress to defeat the missing pulse alarm for a time determined by the missing pulse
delay multiplier.

0 = Normal Run Mode;
1 = Startup Mode – defeat/delay Missing Pulse Alarm
Default = 0 – Normal Run Mode

Bit/Word Definitions for the Block Transfer Write Words

Word

Bit

Definition