Publication 1794-6.5.11 - September 2011

Read and Write Configuration Maps for the FLEX I/O Module 39

Word 5

Bits 00…03

Diagnostic Status – indicates the response from the module; a normal or non-normal
operating condition.

Bit

03

02

01

00

0

0

0

0

0 = Normal Operation (No Failure)

0

0

0

1

1 = Calibration Failure

0

0

1

0

2 = Configuration Failure
A Minimum Frequency Sample Time value other than 0…9
was selected.

0

0

1

1

3 = Message Failure

0

1

0

0

4 = Lead Break Detection Hardware Failure

0

1

0

1

5 = Major Hardware Failure

0

1

1

0

6 = EEPROM Failure

0

1

1

1

7 = RAM Failure

1

0

0

0

8 = ROM Failure

1

0

0

1

9 = Calculation Failure
The actual Frequency is greater than 32,767 Hz. or 3,276.7 Hz.
(overange).
The scaled Frequency is greater than 32,767 Hz. or 3,276.7 Hz.
(overange).
The % Full Scale calculation (based on Maximum Frequency) is
> 3,276.7%.

1010…1111

10…15 = Not Used

Bits 04…15
(04…17)

Reserved

Block Transfer Write Word Assignments

(Octal Bit)

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

0

CF

SSM

FR
Ch 0

Number Of Pulses
To Terminate
Sampling Ch 0

MPM
Ch 0

R

LF

FR
Ch 1

Number Of Pulses To
Terminate Sampling
Ch 1

MPM
Ch 1

1

Maximum Frequency 0…32,767 or 0.0…3,276.7 or Absolute Value of Acceleration 0…32,767 – Channel 0

2

Frequency Scaling Divisor 0…255 Ch 0

Frequency Scaling Multiplier 0…255 Ch 0

3

WOFG
Ch 0

WOFF
Ch 0

IGI
Ch 0

IFI
Ch 0

Minimum Frequency
Sample Time Ch 0

Init
St Up
Ch 0

ACT Ch 0

F/A AS
Ch 0

MPDM
Ch 0

WOFM
Ch 0

4

Maximum Frequency 0…32,767 or 0.0…3,276.7 or Absolute Value of Acceleration 0…32,767 – Channel 1

Bit/Word Definitions for Block Transfer Read Words

Word

Bit

Definition