Rockwell Automation 1794-IJ2XT FLEX I/O Frequency Input Modules User Manual User Manual

Page 58

Advertising
background image

Publication 1794-6.5.11 - September 2011

48 Read and Write Configuration Maps for the FLEX I/O Module

Word 6

Bit 13 (15)

Invert Select – Gate Input (channel 1) – Selects whether to invert the Gate input signal,
if not using an Active High (24V = On) 24V DC IEC 1+ sensor or “Normally Open” relay or
switch contact on the 24V DC Gate Input terminal. Allows compatibility with an Active
Low (0V = On) 24 V DC IEC 1+ sensor or “Normally Closed” relay contact on the 24V DC
Gate Input terminal.

0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On)
Default = 0 – Normal (Active High, 24V = On)

Bit 14 (16)

Wire Off Fault Select – Frequency Input (channel 1) – Selects whether to turn On or Off
the 24V DC Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection.

0 = Disable,
1 = Enable
Default: = 0 – Disable

Note: Customer devices must draw more than 0.4 mA in the On and Off State. To use
this feature with relays or switches, connect a shunt resistor (~ 50K) across the
contacts.

Bit 15 (17)

Wire Off Fault Select – Gate Input (channel 1) – Selects whether to power On or Off the
24V DC Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection.

0 = Disable,
1 = Enable
Default = 0 – Disable

Note: Customer devices must draw more than 4 mA in the On and Off State. To use this
feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.

Input Map

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word

Read

0

Frequency 0…32,767 or 0.0…3,276.7 Channel 0

1

% Full Scale 0.0…3,276.7% Channel 0 or Acceleration -32,768…32,767 Channel 0

2

Frequency 0…32,767 or 0.0…3,276.7 Channel 1

3

% Full Scale 0.0…3,276.7% Channel 1 or Acceleration -32,768…32,767 Channel 1

4

R

R

Direction
Ch 0

GS
Ch 0

F/A
Ch 0

WO
Ch 0

MPA
Ch 0

R

R

Direction
Ch 1

GS
Ch 1

F/A
Ch 1

WO
Ch 1

MPA
Ch 1

5

Reserved

Diagnostic Status
Channel 0

Reserved

Diagnostic Status
Channel 1

6

Reserved

Where:

R = Reserved
GS = Gate state
F/A = Frequency/Acceleration alarm
WO = Wire-off alarm
MPA = Missing pulse alarm

Bit/Word Definitions for the Block Transfer Write Words

Word

Bit

Definition