Publication 1794-6.5.11 - September 2011

14 Install Your FLEX I/O Frequency Input Module

The frequency input module requires 30 mA at 5V DC from the FlexBus
backplane.

Methods of wiring the terminal base units are shown in the illustration below.

Install the Module

Installation of the frequency input module consists of:

• mounting the terminal base unit
• installing the module into the terminal base unit
• installing the connecting wiring to the terminal base unit

Mount on a DIN Rail

Install the Terminal Base Unit

1. Remove the cover plug in the male connector of the unit to which you

are connecting this terminal base unit.

ATTENTION

Total current draw through the terminal base unit is limited to 10 A.
Separate power connections may be necessary.

ATTENTION

Do not daisychain power or ground from the terminal base unit to any
AC or DC digital module terminal base unit.

ATTENTION

Do not remove or replace a terminal base unit when power is applied.
Interruption of the FlexBus can result in unintended operation or
machine motion.

Advertising