Read and Write Configuration Maps for the FLEX I/O Module 47

Word 6

Bit 07

Initiate Startup Select (channel 1) – Alerts a channel that if process startup is in
progress to defeat the missing pulse alarm for a time determined by the missing pulse
delay multiplier.

0 = Normal run mode,
1 = Startup Mode – Defeat/delay Missing Pulse Alarm
Default = 0 – Normal run mode

Bits 08…11
(10…13)

Minimum Frequency Sampling Time (channel 1) – Specifies the minimum time (in ms)
the module will spend collecting pulses to determine the Frequency.

Bit

11

10

09

08

Minimum Frequency Sampling Time (in ms)

0

0

0

0

2

0

0

0

1

4

0

0

1

0

5

0

0

1

1

10

0

1

0

0

20

0

1

0

1

50

0

1

1

0

100

0

1

1

1

200

1

0

0

0

500

1

0

0

1

1000

1010…1111 not used – 2 ms default sample time used

Bit 12 (14)

Invert Select – Frequency Input (channel 1) – Selects whether to invert the Frequency
input signal, if not using an Active High (24V = On) 24V DC IEC 1+ sensor or Normally
Open relay or switch contact on the 24V DC Frequency Input terminal. Allows
compatibility with an Active Low (0V = On) 24V DC IEC 1+ sensor or Normally Closed
relay contact on the 24V DC Frequency Input terminal.

0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On).
Default = 0 – Normal (Active High, 24V = On)

Bit/Word Definitions for the Block Transfer Write Words

Word

Bit

Definition

Advertising