Install the Counter Module

3. To key the RTB in positions that correspond to unkeyed module positions,

insert the straight, wedge-shaped tab on the RTB with the rounded edge
first.

4. Push the tab onto the RTB until it stops.
5. Repeat

step 1

step 4

by using additional U-shaped and straight tabs until

the module and RTB lock into each other properly.

Connect the Wires

Before wiring the module, adhere to these wiring guidelines.

Module Side of RTB

20851-M

0

1 2

3

4 5

6 7

WARNING: If you connect or disconnect wiring while the field-side power is on,
an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.

ATTENTION: If multiple power sources are used, do not exceed the specified
isolation voltage.

ATTENTION: When using the 1756-TBCH, do not wire more than two

0.33…1.3 mm

2

(22…16 AWG) conductors on any single terminal. Use only

the same size wires with no intermixing of solid and stranded wire types.

When using the 1756-TBS6H, do not wire more than one conductor on any single
terminal.