Rockwell Automation 1756-LSC8XIB8I ControlLogix Low-speed Counter Module User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 1756-UM536A-EN-P - April 2012

55

Configure the Module

Chapter 4

3. If you enabled filtering for one or more counters on the Counter

Configuration tab, configure the filter times under Counter Input Filter
Time.

4. In the Hardware Input Filters area, enable filtering for one or more

hardware inputs.

5. If you enabled filtering for one or more hardware inputs, configure the

filter times under Input Filter Time.

6. Click Apply.

Field

Description

Configuration Tag

Off –>On

Enter how long an Off to On transition at a counter must remain
in the On state before the module counts the transition.
Valid filter time = 0…30,000 μs
Default = 0

CounterFilterOffOn

On –>Off

Enter how long an On to Off transition at a counter must remain
in the Off state before the module counts the transition.
Valid filter time = 0…30,000 μs
Default = 0

CounterFilterOnOff

Field

Description

Configuration Tag

Enable Filter
(all input points)

Check the checkbox to enable filtering for hardware input
points 0…7.

Not applicable

Enable Filter
(points 0…7)

Check the checkbox next to one or more input point
numbers to enable filtering on an individual point basis.

PtXFilterEn

Field

Description

Configuration Tag

Off –>On

Enter how long an Off to On input transition must remain in the
On state before the module recognizes the transition.
Valid filter time = 0…30,000 μs
Default = 0

PtFilterOffOn

On –>Off

Enter how long an On to Off input transition must remain in the
Off state before the module recognizes the transition.
Valid filter time = 0…30,000 μs
Default = 0

PtFilterOnOff