Rockwell Automation Publication 1756-UM536A-EN-P - April 2012

Appendix A

Electronic Keying

If you use Disabled Keying, you must take full responsibility for understanding
whether the module being used can fulfill the functional requirements of the
application.

EXAMPLE

In the following scenario, Disable Keying prevents I/O
communication
.

The module configuration is for a 1756-IA16 digital input module. The
physical module is a 1756-IF16 analog input module. In this case,
communication is prevented because the analog module rejects
the data formats that the digital module configuration requests
.

Module Configuration

Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IA16
Major Revision = 3
Minor Revision = 1

Physical Module

Vendor = Allen-Bradley
Product Type = Analog Input Module
Catalog Number = 1756-IF16
Major Revision = 3
Minor Revision = 2

Communication is prevented.