Rockwell Automation Publication 1756-UM536A-EN-P - April 2012
53
Configure the Module
Chapter 4
Configure Hardware
Inputs 0…7
You can tie a counter control function for a designated counter to standard
hardware inputs 0…7. This enables the state of an external input device to invoke
a specific counter function. For more information about counter control
functions, refer to
Counter Control Functions on page 15
.
Follow these steps to configure the module’s standard hardware inputs to invoke
counter control functions.
1. On the Modules Properties dialog box, click the Input Configuration tab.
IMPORTANT
Each of the counter control functions can also be invoked via the output tags
for real-time control. For more information about output tags, see