32

Rockwell Automation Publication 1756-UM536A-EN-P - April 2012

Chapter 3

Install the Counter Module

Spring Clamp

Follow these steps to wire a spring clamp.

1. Strip 11 mm (7/16 in.) maximum length of wire.
2. Insert the screwdriver into the outer hole of the RTB to depress the spring-

loaded clamp.

3. Insert the wire into the open terminal and remove the screwdriver.

The open section at the bottom of the RTB is called the strain relief area. The
wiring from the connections can be grouped with a plastic tie.

RTB Wiring Recommendations

Consider these guidelines when wiring your RTB:

Begin wiring the RTB at the bottom terminals and move up.

Use a tie to secure the wires in the strain relief area of the RTB.

A jumper bar is shipped with certain I/O modules to assist in installation.

Additional jumper bars can be purchased in packages of 25 by ordering
catalog number 1756-JMPR.

For applications that require heavy gauge wiring, order and use an

extended-depth housing, catalog number 1756-TBE.

IMPORTANT

Make sure the wire, and not the screwdriver, is inserted into the open terminal
to prevent damage to the module.

20860-M

Strain Relief Area