Input tags – Rockwell Automation 1756-LSC8XIB8I ControlLogix Low-speed Counter Module User Manual

Page 73

Advertising
background image

Rockwell Automation Publication 1756-UM536A-EN-P - April 2012

73

Tag Definitions

Appendix B

Input Tags

The input tags in

Table 6

indicate the current status of input points. The input

module sends this data to the controller or peer output module for processing.

Table 6 - Counter Module Input Tags

Name

Data Type

Definition

Fault

DINT

Fault—Indicates whether a fault has occurred. The controller sets all 32 bits upon a connection loss.
Fault bits 8…15 are also set by these conditions:
Negative values in one or more of the Counter[x].Rollover, Counter[x].Preset, Counter[x].Window0On,

Counter[x].Window0Off, Counter[x].Window1On, or Counter[x].Window1Off output tags

Preset value >rollover value

Pt[x].Data

BOOL

Data—Indicates the current On/Off value of the corresponding hardware input.
0= Off
1 = On

Counter[x].Count

DINT

Accumulated Count—Indicates the accumulated count value currently detected by Counter[x].
Valid values are 0…2

31

Counter[x].Frequency

REAL

Instantaneous Frequency—Indicates the frequency of the last pulse detected by a counter.
Valid values are

0.0

For details about how the module calculates instantaneous frequency, see

Table 3 on page 12

.

Counter[x].FreqAverage

(1)

REAL

Average Frequency—Indicates the average frequency of pulses detected by Counter[x]. The modules calculates
average frequency over the number of pulses defined in the Counter[x].FreqAveragePulseCount configuration tag.
Valid values are

0.0

For details about how the module calculates average frequency, see

Table 3 on page 12

.

Counter[x].PulseWidth

REAL

Instantaneous Pulse Width—Indicates the duration in microseconds of the last rising pulse edge to falling pulse
edge. The accuracy of the instantaneous pulse width is always ± -11 μs regardless of the actual pulse width.
Valid values are

0.0

Counter[x].PulseWidthAverage

(1)

REAL

Average Pulse Width—Indicates the average width of pulses. The module calculates average pulse width over the
same number of pulses used to calculate the average frequency of pulses.
Valid values are

0.0

For details about how the module calculates average pulse width, see

Table 3 on page 12

.

Counter[x].CountSequence

SINT

Count Sequence—Stores a rolling sequence number for each new count. The value increments each time a new count
is broadcast to the backplane.
Valid values are -128…127

Counter[x].FrequencySequence

SINT

Frequency Sequence—Stores a rolling sequence number for each new average frequency. The value increments each
time a new average frequency is calculated.
Valid values are -128…127

Counter[x].PulseWidthSequence

SINT

Pulse Width Sequence—Stores a rolling sequence number for each new average pulse width. The value increments
each time a new average pulse width is calculated.
Valid values are -128…127

Counter[x].Data

BOOL

Data—Indicates the current On/Off value of the corresponding counter input.
0= Off
1 = On