Software diagnostics – Rockwell Automation 1756-LSC8XIB8I ControlLogix Low-speed Counter Module User Manual

Page 58

Advertising
background image

58

Rockwell Automation Publication 1756-UM536A-EN-P - April 2012

Chapter 5

Troubleshoot the Module

Software Diagnostics

In addition to the status indicators on the module, RSLogix 5000 software alerts
you to fault conditions. The software reports fault conditions in these ways:

A warning icon appears next to the module in the I/O Configuration

tree (

Figure 16

) when the controller-to-module connection is lost. If the

connection between the counter module and a peer output module is lost,
the counter module continues to communicate with the controller, and no
fault indication appears.

Figure 16 - Fault Notification in I/O Configuration Tree

The Module Info tab on the Module Properties dialog box displays the

module’s status along with major and minor faults (

Figure 17

).

Figure 17 - Module Status and Faults on Module Info Tab