Configure the Module

4. Use program logic or the RSLogix 5000 tag editor to define the following

values or counter control functions in the module’s output tags.

For more information about module tags, refer to

Appendix B

.

Value or Counter Control Function

Output Tag

Window On/Off

Counter[x].Window0On, Counter[x].Window0Off
Counter[x].Window1On, Counter[x].Window1Off

Preset

Counter[x].Preset

Rollover

Counter[x].Rollover

Count Enable

Counter[x].DisableCount

Reset Count

Counter[x].ResetCount

Preset Count

Counter[x].PresetCount

Up/Down Count

Counter[x].CountDown

IMPORTANT

In RSLogix 5000 software, versions 18.02.00 and later, output tag
information is sent to the counter module only at the RPI rate defined
during configuration. For optimal performance, use an Immediate
Output (IOT) instruction.

For example, the rung shown below contains an IOT instruction for a
counter module in slot 3. Add a similar rung to your last routine within
the Main Task to mimic normal output tag processing.