Rockwell Automation 1756-LSC8XIB8I ControlLogix Low-speed Counter Module User Manual

Page 51

Advertising
background image

Rockwell Automation Publication 1756-UM536A-EN-P - April 2012

51

Configure the Module

Chapter 4

3. Complete the fields as described in the table below and click Apply.

Field

Description

Configuration Tag

Calculate Average Frequency Over

Type the number of pulses to use to calculate average frequency. This value is also
used to calculate average pulse width. For more information about how average
frequency and average pulse width are calculated, see

page 12

.

Valid values = 0…1, 000
Default = 10

Counter[x].FreqAveragePulseCount

Frequency Calculate Timeout

Type the amount of time in milliseconds the counter will wait between pulses before
it sets the input frequency to zero.
Valid values = 0…10, 000 ms
Default = 1,000 ms

Counter[x].FreqTimeout

Enable Filter for this Counter

Check the checkbox to enable filtering. When filtering is enabled, transitions at a
counter must remain in the new state for a configured length of time before the
module begins counting. You can configure the filter time on the Input Configuration
tab.

Counter[x]FilterEn

Window 0 Defined In

From the pull-down menu, choose the method window 0 will use to evaluate
incoming pulses.
Valid values:
Counts (default)
Frequency
Average Frequency

Counts:
Counter[x].Window0UsesFreq = 0
and
Counter[x].Window0FreqAverage = 0

Frequency:
Counter[x].Window0UsesFeq = 1
and
Counter[x].WindowFreqAverage = 0

Average frequency:
Counter[x].Window0UsesFeq = 1
and
Counter[x].WindowFreqAverage=1

Window 1 Defined In

From the pull-down menu, choose the method window1 will use to evaluate
incoming pulses.
Valid values:
Counts (default)
Frequency
Average Frequency

Counts:
Counter[x].Window1UsesFreq = 0
and
Counter[x].Window1FreqAverage = 0

Frequency:
Counter[x].Window1UsesFeq = 1
and
Counter[x].WindowFreqAverage = 0

Average frequency:
Counter[x].Window0UsesFeq = 1
and
Counter[x].WindowFreqAverage=1