Rtb types – Rockwell Automation 1756-LSC8XIB8I ControlLogix Low-speed Counter Module User Manual

Page 31

Advertising
background image

Rockwell Automation Publication 1756-UM536A-EN-P - April 2012

31

Install the Counter Module

Chapter 3

Use an RTB

(1)

or interface module (IFM) to connect wires to your module. To

use an RTB, follow the directions below to connect wires to the RTB. IFMs are
prewired prior to shipping. The counter module supports IFM catalog numbers
1492-IFM40F, 1492-IFM40DS24A-4, 1492-IFM40F-FS24A-4, and
1492-IFM40F-FSA-4.

RTB Types

Use one of these types of RTBs with your counter module:

Cage clamp, catalog number 1756-TBCH
Spring clamp, catalog number 1756-TBS6H

Each RTP comes with housing. Wire the RTB with a 3.2 mm (1/8 in.) maximum
screwdriver before installing it onto the module.

Cage Clamp

Follow these steps to wire a cage clamp.

1. Strip 9.5 mm (3/8 in.) maximum length of wire.
2. Insert the wire into the open terminal on the side.
3. Turn the screw clockwise to close the terminal on the wire.

The open section at the bottom of the RTB is called the strain relief area. The
wiring from the connections can be grouped with a plastic tie.

(1) The ControlLogix system has been agency certified using only the ControlLogix RTBs (1756-TBCH, 1756-TBNH, 1756-TBSH, and

1756-TBS6H). Any application that requires agency certification of the ControlLogix system using other wiring termination methods
may require application specific approval by the certifying agency.

ATTENTION: The ControlLogix system has been agency certified using only the
ControlLogix RTBs 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H). Any
application that requires agency certification of the ControlLogix system using
other wiring termination methods may require application specific approval by
the certifying agency.

20859-M

Strain Relief Area

Advertising